Rose Remodeling & Construction, LLC 9045 Hawthorne Avenue, Surfside, Florida · Single-Family New Construction · Jeffrey R. Rose, President 5 disciplines · 41 sheets

The Entire Report, Published: 21 Findings on a Surfside Custom Home

A returning builder let us publish the whole thing under the project’s real name. Every finding, every cited sheet, every recommended action, open to anyone.

Impact at a glance

Most plan review claims are a number in a slide deck. This one is the actual report, published in full, on a named project you can look up.

21
Findings returned
$69,878–$219,817
Flagged exposure
16 of 21
From the calc and energy package
ClientRose Remodeling & Construction, LLC
Project9045 Hawthorne Avenue, Surfside, Florida
Set reviewed41 sheets across 5 disciplines, plus 165 pages of calculations and reports
Findings21 returned – 1 Critical, 6 High, 8 Medium, 6 Low
The one that leadsF002 – gas sleeve through the structural slab, uncoordinated
Flagged exposure$69,878 – $219,817, pre-construction
Review dateSeptember 17, 2026
Published withWritten permission of the owner and builder

Read the actual report

Not a summary and not a redacted sample. The full interactive report for this project, with the real sheet numbers and the drawings behind every finding.

Open the 9045 Hawthorne report →

The Challenge

Rose Remodeling and Construction came back to Flikt.AI with a second project, a new single-family residence at 9045 Hawthorne Avenue in Surfside, Florida. The permit set ran 41 sheets across Structural, Architectural, Electrical, Plumbing and Mechanical, and it arrived with the full supporting package rather than the drawings on their own. That package carried 165 pages of structural calculations, energy and Manual J load reports, the boundary survey, and the subsoil and percolation investigations.

A conventional coordination review rarely opens those documents, because reading a calculation package line by line against the drawings is slow work that does not fit a preconstruction schedule. On this project that is exactly where most of the findings turned out to live.

What Flikt.AI Flagged

The review returned 21 findings: one Critical, six High, eight Medium and six Low, carrying a combined flagged cost exposure of $69,878 to $219,817. Sixteen of the 21 came from reading the specification, calculation and energy package against the drawings, which is coordination work a sheet-by-sheet pass structurally cannot perform. Three of the findings are worth walking through.

F002 · Critical · Plumbing / Structural
Gas Piping Sleeve Through Structural Slab Not Coordinated

The gas plan P-106 shows a PVC sleeve carrying gas piping through the concrete slab to the kitchen island cooktop, noted as compliant with Section 404.6 of the Florida Fuel Gas Code. The structural ground floor plan S-3.0 shows the 8″ slab and its reinforcement, but indicates no sleeve or penetration at that location. The structural notes do require sleeves for all piping passing through foundations, slabs or masonry walls, yet no specific sleeve location is coordinated between the gas plan and the structural plan.

Affected Sheets: P-106, M-103, S-3.0, S-8.0  ·  Estimated Cost Exposure: $6,625 – $20,750
F008 · High · Electrical
Panel AIC Rating Contradicts Itself on the Same Sheet

On sheet E-106 the panel schedules for Panel A and Panel B both list an interrupting rating of 10,000 AIC in their headers. The riser diagram printed on that same sheet specifies both panels and the main disconnect at 22K AIC. The set therefore carries two different fault-current ratings for the same equipment, roughly a sheet apart, which is a difference that matters for fault current protection rather than a drafting nuisance.

Affected Sheets: E-106  ·  Estimated Cost Exposure: $8,000 – $25,000
F021 · Medium · Mechanical / Architectural
Bathroom Exhaust Penetrations Missing From the Roof Plans

Mechanical plan M-102 calls out 4″ exhaust ducts through the roof with cap and bird screen at Bathroom #5, Bathroom #1 and the Master Bathroom. The architectural roof plan A-203 shows no penetration locations for any of them, and the structural roof plan S-5.0 shows pre-engineered wood trusses without indicating where those penetrations fall. Each of those roof penetrations needs to clear a truss and needs a flashing detail, and neither question is answered anywhere in the set.

Affected Sheets: M-102, M-103, A-203, S-5.0  ·  Estimated Cost Exposure: $1,933 – $6,167

Why Findings Like These Survive Sign-Off

None of the three above is a mistake by anybody on the design team. Each one survives review for a structural reason, and the reasons repeat from project to project:

  • The conflict lives between two sheets that different people drew. The plumbing engineer drew a correct sleeve detail and the structural engineer drew a correct slab, so the only place the problem exists is in the comparison that nobody was assigned to make.
  • The calculation package is treated as backup rather than as drawings. Energy models, Manual J runs and structural calcs get submitted, stamped and filed, and they very rarely get read back against the sheets they are supposed to describe.
  • An internal contradiction reads as correct on either page alone. A reviewer looking at the panel schedule sees a valid rating, and a reviewer looking at the riser sees a valid rating, so the contradiction only appears when the two are held side by side.

Flikt.AI reads the white space between drawings, and it reads the package behind them. That is the job.

Published With Permission

Jeffrey R. Rose · President, Rose Remodeling and Construction, LLC

The owner and builder of 9045 Hawthorne Avenue gave Flikt.AI written permission to publish this project under its real name, including the full report, the real sheet numbers and the drawings behind each finding. Construction value is not disclosed at the client’s request.

Key Takeaway

Twenty-one coordination findings came back on a single-family permit set that had already been drawn, sealed and assembled for submission, and sixteen of them were only visible to a reviewer willing to read 165 pages of calculations against 41 sheets of drawings. That is the reading almost nobody has time to do by hand, and it is the reading that produces the gas sleeve, the contradictory panel rating and the unplanned roof penetrations.

Rather than ask you to take the finding count on faith, we published the report. Open it, pick any finding, and check it against the sheet it cites.

Want to see what Flikt.AI can find in your plans?

Submit Plans for a Quote Book a Demo

Already built the project? Send the bid-time set and its RFI log and check findings like these against what your team actually asked for in the field.

Note: This project is published under its real name and address with the written permission of the owner and builder. Findings, sheet references and cost estimates are reproduced from the actual Plan Coordination Report delivered on September 17, 2026.